433 Central Ave., 4th Floor, St. Petersburg, FL 33701 | [email protected] | Office: (727) 493-2351

1. EXECUTIVE SUMMARY

  • CVSS v3 6.5

  • ATTENTION: Low skill level to exploit
  • Vendor: AVEVA
  • Equipment: InduSoft Web Studio, InTouch Edge HMI
  • Vulnerability: Uncontrolled Search Path Element

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow execution of unauthorized code or commands.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of AVEVA InduSoft Web Studio and InTouch Edge HMI are affected by a vulnerability in a third-party component, Gemalto Sentinel UltraPro encryption keys.

  • InduSoft Web Studio versions prior to v8.1 SP3
  • InTouch Edge HMI versions prior to 2017 Update 3

3.2 VULNERABILITY OVERVIEW

3.2.1    UNCONTROLLED SEARCH PATH ELEMENT CWE-427

The uncontrolled search path element vulnerability allows an attacker to load and execute a malicious REVERB1 dynamic link library (dll) in third-party component Sentinel UltraPro.

CVE-2019-6534 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy, Transportation Systems, and Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United Kingdom

3.4 RESEARCHER

ADLab of Venustech reported this vulnerability to NCCIC.

4. MITIGATIONS

AVEVA recommends that users upgrade to the latest versions located the following links:

InduSoft Web Studio v8.1 SP3

http://download.indusoft.com/81.3.0/IWS81.3.0.zip

InTouch Edge HMI 2017 Update 3

https://softwaresupportsp.schneider-electric.com/#/producthub/details?id=52354 (login required)

Users who are unable to upgrade to the latest version of InduSoft Web Studio or InTouch Edge HMI, can alternatively apply Security Update LFSec131:

http://www.indusoft.com/download/patches/security/LFSec131.zip 

https://softwaresupportsp.schneider-electric.com/#/producthub/details?id=52410 (login required)

For addition information please see AVEVA Security Bulletin LFSEC00000131:

https://sw.aveva.com/hubfs/assets-2018/pdf/security-bulletin/SecurityBulletin_LFSec131.pdf

NCCIC recommends users take the following measures to protect themselves from social engineering attacks:

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.